Machine Room Requirements

The machine room size as shown is minimum, other sizes and shapes can be accommodated. Please consult DEM EE for details.

Notes: 
  • Equipment requires a legally constructed and enclosed machine room, adequately lighted, and conditioned to maintain temperature between 60° to 90° Fahrenheit, relative humidity is not to exceed 90% non-condensing.
  • Machine room must be of adequate size to provide clearances around and between equipment as required by code.
  • Requires a fused disconnect switch for each elevator in the machine room, located in a position based on local code and within sight of elevator equipment, and arranged to be locked in the off position
  • Requires 110 VAC service for elevator light and accessories connected to the car light service terminal on the elevator A single disconnecting means for the car light and accessories shall be located in the machine room and arranged to be locked in the open position.
  • Requires light, switch and 110 VAC GFI outlet in the machine room, with switch located adjacent to the machine room
  • Only elevator related equipment is allowed in machine room.

Locked Rotor AMPS are given for Wye-Delta starting.  Starting AMPS are 3 times Locked Rotor AMPS when starting across the line.

HPVoltFull Load AmpsLocked Rotor Amps (Wye-Delta)
152085182
15230/46045/22.568/34
2020866104
20230/46056/2890/45
2520878130
25230/46068/34113/57
3020890157
30230/46078/39136/68
40208120224
40230/460104/52195/97
50208142307
50230/460123/62268/133

Electrical Data for Hydraulic 3 Phase Motors (80 Starts Per Hours) in a Submersible Power Unit

DEM EE can provide not only standard sizes as outlined above but also non-standard or custom sizes. Please consult DEM EE for details.